FLOW RATE TOTALISER

UT-1210

  • BTU / TR TOTALIZER

     

    ♦ Accepts up to three inputs– FLOW ( mA ), TEMPERATURES-1 (RTD), TEMPERATURES-2 (RTD).

    ♦ Isolated 0/4-20mA retransmission output Proportional to standard flow rate.

    ♦ Multi Parameter Auto scroll display like temp. in and temp. out and total.

    ♦ Non-volatile memory to retain totaliser flow, no need of battery to change.

    ♦ FIT-used in chilled water,condenser water, and hot water systems.

    ♦ The engineering unit can be selected as either KW & KWHR or BTU/Hr & BTU.

    ♦ Based on calculations of thermal power & energy consumed through measurement of floe, temperature diffrence of inlet & outlet of the medium.

  •  FEATURE

     

    ♦ Multi Parameter Auto scroll display like temp. in and temp. out and total.

    ♦ Accepts up to three inputs– FLOW ( mA ), TEMPERATURES-1 (RTD), TEMPERATURES-2 (RTD)

    ♦ Non-volatile memory to retain totaliser flow, no need of battery to change.

    ♦ Isolated 0/4-20mA retransmission output Proportional to standard flow rate

    ♦ Field operated User friendly menu for device Configurations & Calibration.

    ♦ 8/10 digit Flow Totaliser with password protected resetting.

    ♦ Fully password protection for Tamper free operation.

    ♦ Isolated Highly communicative serial interface facility (RS 232/485).

    ♦ 24 V loop power supply for flow.

    ♦ Optional GSM mobile connectivity for Wireless Remote reading purpose.(SMS)

    ♦ Flow Metering computer software available.

    ♦ Weather proof or flame proof housing.

► Input

Flow - 0 - 20mA DC, 4-20mA DC, 0 - 10VDC

Temperatures - 1 - RTD PT - 100 3 wire / 4-20mA

Temperatures - 2 - RTD PT - 100 3 wire / 4-20mA

Transmitter power supply -24VDC @ 30mA max, isolated from I/P & O/P

Range limets -0.1 to 99999 Programable with decimal point selection

Accuracy -+/- 0.25 % of span

Input impedance ->330 K for Voltage & 100 R for current

Input mode -Linear or square root

► INDICATION

Indication - LED TYPE : 5 digit Flow rate & 10 digit Totalizer - 16x2 line LCD

Status indication -Parameter display

Parameter display - Temperature in / Temperature Out / TR total

► OUTPUT

Communication - Modbus RTU RS- 485 / RS - 232 communications

Analog Current & Voltage output -0-20/ 4-20mA, 0-5V, 0-10V, 1-5VDC, fully 3 port isolated

Wireless communication - GSM / GPRS base mobile (sms) communication

► COMMUNICATION

Communication Protocol & method - Modbus RTU RS- 485 / RS - 232 communications

Programeble parameter & Connectable number -Baud rate, Parity, Node address, stop bit. & 0-256 unit

Wireless communication - GSM / GPRS base mobile (sms) communication

► PROGRAMMBALE PARAMETERS

Display resolution - Temperature in / Temperature Out / TR total

Programming of parameters - Through 4 tactile key

► Other

(A)Dimensions (B)Panel cutout(C) Mounting -(A)96(H) x 96 (W) x 100 (D) (B)92 x 92 (C)Panel mounted

(A) Supply voltage (B) Power consumption - (A)110/230VAC, 50/60 Hz (B)4 watt maximum

Operating ambient Temperature and Humidity - • 0~50 °C • Below 90%, non condensing

► Flame Proof

Gas group - I IIA IIB as per IS 2148/1981

Enclose certification - Enclosure is certifies by C.M.R.I. Dhanbad

Display glass - Clear glass thognet type A as per IS 2206

Degree protection - IP 65 as per IS 2147

Material of constructions -Aluminum alloy

Cable entry -5 x 3/4 “ ET

External keys -4 nos push button