INDICATOR CONTROLLER

UT-1803

  • LARGE TEMP+RH+TIME DISPLAY

     

    ♦ Large display size 2”/4”/12” available.

    ♦ Real time display with rechargeable battery backup.

    ♦ Hanging/Rack/wall/panel mounting options.

    ♦ Highly stable built-in or Remote Temp.+ RH sensor.

    ♦ Potential Free Relay contact output up to 2 nos.

    ♦ All Configurations and calibration from front panel keypad.

  •  FEATURE

     

    ♦ Large display size 2”/4”/6”/8”/12”/16” available.

    ♦ Large display size for easy viewing from a distance.

    ♦ Hanging /Rack/wall/panel mounting options with IP protection.

    ♦ Micro controller based indicator with inbuilt Temp.+ RH +Time measurement in single enclosure.

    ♦ All channel are programmable ranges and unit (Through Front key pad).

    ♦ Incorporates highly stable built-in Temp.+ RH sensor.

    ♦ Different size of display for displaying RH & Temperature and 4 digit for time.

    ♦ Process parameter High and Low LEDs status indication for all three channels.

    ♦ MODBUS RTU multi drop RS-485 serial communication for PLC, SCADA etc.

    ♦ Password protection for calibration and programming mode.

    ♦ Software Calibration for 3 channels.

    ♦ Programmable Device address, Baud rate, Parity and Stop bit.

    ♦ Local programing facility for real time with battery backup.

    ♦ User programmable offset correction.

    ♦ Brick/Wall mounting and panel mounting enclosure with IP protection.

    ♦ Optional GSM mobile connectivity.

► Input

Nos. of input - 1-(TEMP + RH) , 2-(TEMP.+RH+REAL TIME)

Temperature input - Integral or Remote(external:4-20 mA or 0-10 V /RTD PT-100)

Humidity input - Integral or Remote (external:4-20 mA or 0-10 V DC)

Transmitter power supply - 24V/5V DC @ 30 mA max, isolated from I/P & O/P

► Indication

Temperatures -Channel-1: 3 digit Seven segments 1”/2”/4”/6”/12”/16” display.

Humidity -Channel-2: 3 digit Seven segments 1”/2”/4”/6”/12”/16” display.

TIME -Channel-3: 4 digit Seven segments 1”/2”/4”/6”/12”/16” display.

► Range

Temperatures -0 to 60.0 *C with decimal point.

Humidity -0 to 99.9 % with decimal point.

Time -Hour : Minute 12 or 24 hour formats 00:00

Display Resolution -0.1 for Temp. & Rh

► Accuracy

Temperatures -0.25 % on FS Response time : 8 sec

Humidity -2.5 % for 10 to 90 % RH rest of 3% Response time : 4 sec

Time -0.01 % Response time : 1 sec

► Communication

Communication Protocol -Modbus RTU RS- 485 Isolated communications.

Programmable parameter -Baud rate , Parity , Node address , stop bit.(minute and hour)

Read /write parameter -Read: Process value ,decimal point. Write: Hi Low set point.

No. of slave ID -Total 1-256 unit.

► Parameters

Set point / High scale / Low scale -Full range as per input selection.

Programming of parameters -Through 4 tactile keys (with password protections)

Alarm logic -Full Scale HI OR Full scale Low

► Other

Mounting -Bricks and modules wall Flush panel mounting

Enclosure MOC -M S powder coated enclosure

Supply voltage Power consumption -230 V DC & as per on display size

Operating ambient temperature and humidity -Temp: 0~60 °C Humidity: Below 90%, non condensing