OTHER

UT-801

  • RPM/MPM INDICATOR CONTROLLER

     

    ♦ Accepts pulses from of PNP/NPN proximity, encoder, limit switch.

    ♦ Programmable multiplication and division factor (pulses/revolution).

    ♦ Can operate with max frequency up to 25kHz.

    ♦ Fast response time as fast as input frequency.

    ♦ Optional Retransmission 4-20 mA and transmitter power supply.

    ♦ Up to 4 number of potential free contact outputs.

  •  FEATURE

     

    ♦ µP Based Power, full & highly reliable controller.

    ♦ Wide range from up to 9,999 R.P.M.

    ♦ Accepts inputs like proximity switch, photo sensors, voltage pulses.

    ♦ P.P.R. Multipliers and quartz crystal time base.

    ♦ No mechanical moving parts

    ♦ Transmitter P.S. @ 12/24V DC.

    ♦ Gives max. 4 on/off outputs.

    ♦ Retransmission output on Speed.

    ♦ Various sizes / Mountings / Enclosures supported.

    ♦ RS-485/232 Comm. O/P provided

    ♦ Power supply :230V/110V AC. Or 24V/12V DC

    ♦ Isolated 0/4-20mA process value retransmission output.

► Input

Input Type -PNP / NPN Proximity ( NC type ) – 3 wire

PNP / NPN Proximity ( NO type ) – 3 wire

Magnetic pickup – 2/3 wire

Namur type – 2/3 wire

User is required to give Blow Parameter like PPR ratio,Setpoint / Alm. Type/ Hyst.. ( for c/o o/p ) Z and S ( for retransmission )

Transmitter power supply -24 V DC @ 30 mA max, isolated from I/p & O/P.

Range limits -Programable -0 to 9999 with decimal point.

Accuracy -+/- 0.25 % of span

► Indication Control Mode

Indication -4 digit 7 segment display for PV display

Status indication -LEDs for Relay status & Communications

► Output

On Off control -Relays

Relay Output -NO - C - NC Contacts , 5A@240 V AC Resistive / 1 / 2 / 3 / 4 Relays / SSR output

Retransmition Current & Voltage outputs -4~20, 0~5V, 0~10V, 1~5V DC, fully 3 port isolated 1.5KV

► Communication

Communication Protocol & mathode -Modbus RTU RS- 485/RS- 232 communications.

Programeble parameter & Connectable number -Baud rate , Node, Parity , nodeaddress , stop bit. & 0-256 unit.

► Parameters

Setpoint / Hysteresis / High scale / Low scale -Full range as per input selection.

Relay logic -F.S. high & low alarm

Display resolution -0 to 9999 fully configurable for linear input

Programming of parameters -Through 4 tactile keys

► Other

Mounting -Panel mounted

(A) Supply voltage (B) Power consumption -(A)- 110/230 V AC, 50/60 Hz (B) 4 watts maximum

Operating ambient temperature and humidity -0~50 °C / Below 90%, non condensing